1086A Datasheet
The Belden 1086A is a multi-conductor UL instrumentation cable consisting of 24 triad 20 AWG and one 22 AWG bare copper stranded conductors with PVC insulation, individual and overall Beldfoil shielding, and a black PVC outer jacket. It is rated for a voltage of 300V (PLTC/CMG) or 150V (ITC) and operates within a temperature range of -30°C to +105°C. This cable is designed for suitable applications including industrial control systems, DCS, PLCs, solenoids, valves, and low-voltage digital control circuits.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
1086A Key Specifications
- Max Current
- 3 Amps per conductor @ 25°C
- Voltage Rating
- 300 V (CMG, PLTC, UL AWM 2464), 150 V (ITC)
- Operating Temperature
- -30°C to +105°C (UL temperature rating 105°C)
- Conductor Config
- 24 Triads of 20 AWG (7x28) plus 1 Comm wire of 22 AWG (7x30), bare copper
- Max Pull Tension
- 1250 lbs (567 kg)
- Nominal Conductor DCR
- Triads: 9.5 Ohm/1000ft (31 Ohm/km); Comm: 14.7 Ohm/1000ft (48.2 Ohm/km)
- Outer Jacket
- Black PVC, nominal thickness 0.074 in (1.9 mm), nominal diameter 1.079 in (27.41 mm)
- Shielding
- Individual and overall Beldfoil (Alum+Poly) tape with 100% coverage, with drain wires
Characteristics (datasheet)
- Voltage Rating
- 300 V (CMG, PLTC, UL AWM 2464), 150 V (ITC)
- Operating Temperature
- -30°C to +105°C (UL temperature rating 105°C)
- Conductor Config
- 24 Triads of 20 AWG (7x28) plus 1 Comm wire of 22 AWG (7x30), bare copper
- Max Current
- 3 Amps per conductor @ 25°C
- Shielding
- Individual and overall Beldfoil (Alum+Poly) tape with 100% coverage, with drain wires
- Outer Jacket
- Black PVC, nominal thickness 0.074 in (1.9 mm), nominal diameter 1.079 in (27.41 mm)
- Max Pull Tension
- 1250 lbs (567 kg)
- Nominal Conductor DCR
- Triads: 9.5 Ohm/1000ft (31 Ohm/km); Comm: 14.7 Ohm/1000ft (48.2 Ohm/km)
1086A Applications
- Industrial control
- Raceways, cable trays, and ducts
- Digital control
- Instruments (4-20mA, 0-10V)
- Low voltage digital control (24V)
- RTD and control circuits
- Distributed control system (DCS)
- Programmable logic controller (PLC)
- Solenoids, valves, actuators, and positioners
Other Belden parts
- 5521FE — The Belden 5521FE is a security and commercial audio cable designed for indoor r...
- 1863A — The Belden 1863A is an unshielded speaker cable consisting of two 18 AWG strande...
- 1579 — The Belden 1579 is a single-conductor 14 AWG tinned copper hook-up wire with PVC...
- 27080A — The Belden 27080A is a UL Type TC power and control cable containing two 14 AWG...
- 84316 — The Belden 84316 is a commercial, non-QPL Mil-Spec coaxial cable with a 50 Ohm c...
- 5286C — The Belden 5286C is an XTRAGUARD 1 multi-conductor cable featuring 6 pairs of 20...
- 57004 — The Belden 57004 is a plenum-rated, shielded 4-conductor 24 AWG bare copper cabl...
- 76022 — The 76022 is a 4-pair 24 AWG bare copper industrial Ethernet cable featuring pol...
More Bulk Wire Cable
- 78092 — The Belden 78092 is a 2-pair, 20 AWG tinned copper communication cable with modi...
- 4209FE — The Belden 4209FE is a security and commercial audio cable featuring 12 stranded...
- 78088 — The Belden 78088 is an ECOCABLE consisting of 8 pairs of 22 AWG tinned copper co...
- 2177A — The Belden 2177A is a low-loss serial digital coaxial cable (RG-7 type) featurin...
- 5690 — The Belden 5690 is a 2-pair, 26 AWG tinned copper cable with semi-rigid PVC insu...
- 1872A — The Belden 1872A is a Category 6+ premise horizontal cable with a 350 MHz bandwi...
- 2464C — The Belden 2464C is a communication and control cable featuring 2 conductors (1...
- 9939 — The Belden 9939 is a computer EIA RS-232 cable constructed with three 22 AWG str...
1086A FAQ
What is 1086A?
1086A is a Bulk Wire Cable from Belden. The Belden 1086A is a multi-conductor UL instrumentation cable consisting of 24 triad 20 AWG and one 22 AWG bare copper stranded conductors with PVC insulation, individual and overall Beldfoil shielding, and a black PVC outer jacket. It is rated for a voltage of 300V (PLTC/CMG) or 150V (ITC) and operates within a temperature range of -30°C to +105°C. This cable is designed for suitable applications including industrial control systems, DCS, PLCs, solenoids, valves, and low-voltage digital control circuits.
Who manufactures 1086A?
1086A is manufactured by Belden.
Where can I download the 1086A datasheet PDF?
The 1086A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 1086A specifications
Click to ask a quick question:
Parameters
| Conductor Config | 24 Triads of 20 AWG (7x28) plus 1 Comm wire of 22 AWG (7x30), bare copper |
| Max Current | 3 Amps per conductor @ 25°C |
| Max Pull Tension | 1250 lbs (567 kg) |
| Nominal Conductor DCR | Triads: 9.5 Ohm/1000ft (31 Ohm/km); Comm: 14.7 Ohm/1000ft (48.2 Ohm/km) |
| Operating Temperature | -30°C to +105°C (UL temperature rating 105°C) |
| Outer Jacket | Black PVC, nominal thickness 0.074 in (1.9 mm), nominal diameter 1.079 in (27.41 mm) |
| Shielding | Individual and overall Beldfoil (Alum+Poly) tape with 100% coverage, with drain wires |
| Voltage Rating | 300 V (CMG, PLTC, UL AWM 2464), 150 V (ITC) |