1061A Datasheet
The Belden 1061A is a 36-pair instrumentation and control cable featuring 20 AWG and 22 AWG bare copper conductors with PVC insulation, an overall Beld foil shield, and a black PVC outer jacket. It is rated for 300V PLTC and ITC applications with an operating temperature range of -30°C to +105°C. This cable is designed for use in industrial control systems, raceways, cable trays, DCS, PLCs, and connecting instruments, encoders, solenoids, valves, and actuators.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
1061A Key Specifications
- Max Current
- 3 Amps per conductor @ 25°C
- Nom. Capacitance Cond-to-Cond
- 30 pF/ft (98 pF/m)
- Nom. Capacitance Cond-to-Shield
- 55 pF/ft (180 pF/m)
- Nom. Inductance
- 0.19 µH/ft (0.62 µH/m)
- Voltage Rating
- 300 V (CMG, PLTC, UL AWM 2464), 150 V (ITC)
- Operating Temperature
- -30°C to +105°C
- UL Temperature
- 105°C
- Conductor Configuration
- 36 Pair(s) 20 AWG 7x28 BC, 1 Comm Wire(s) 22 AWG 7x30 BC
Characteristics (datasheet)
- Voltage Rating
- 300 V (CMG, PLTC, UL AWM 2464), 150 V (ITC)
- Operating Temperature
- -30°C to +105°C
- UL Temperature
- 105°C
- Max Current
- 3 Amps per conductor @ 25°C
- Conductor Configuration
- 36 Pair(s) 20 AWG 7x28 BC, 1 Comm Wire(s) 22 AWG 7x30 BC
- Nominal Outer Diameter
- 0.980 in (24.9 mm)
- Outer Shield
- Bi-Laminate (Alum+Poly) Tape 100% Coverage, 20 AWG (7x28) TC Drainwire
- Nom. Capacitance Cond-to-Cond
- 30 pF/ft (98 pF/m)
- Nom. Capacitance Cond-to-Shield
- 55 pF/ft (180 pF/m)
- Nom. Inductance
- 0.19 µH/ft (0.62 µH/m)
1061A Applications
- Industrial control
- Raceways, cable trays and ducts
- Digital control
- Instruments (4-20ma, 0-10v)
- Low voltage digital control (24v)
- Encoders
- Control circuits
- Distributed control system (DCS)
- Programmable logic controller (PLC)
- Solenoids, valves, actuators, positioners
Other Belden parts
- 86225CY — The Belden 86225CY is a 25-conductor, 24 AWG tinned copper XTRAGUARD FLEX contin...
- 78324 — The Belden 78324 is a 4-conductor, 24 AWG tinned copper ECOCABLE designed for da...
- 5854 — The Belden 5854 is a single-conductor hook-up wire featuring 24 AWG silver-plate...
- 9434 — The Belden 9434 is a 50-conductor electronic cable made of 22AWG (7x30) tinned c...
- 1481A — The Belden 1481A is a multi-pair instrumentation cable containing 36 pairs of 18...
- 3050 — The Belden 3050 is a single-conductor hook-up wire featuring a 24 AWG tinned cop...
- 7413W — The Belden 7413W is a high-flex MachFlex™ tray cable (TC-ER / WTTC) featuring 6+...
- 7201A — The Belden 7201A is a high-flex MachFlex™ shielded cable featuring two 24 AWG ba...
More Bulk Wire Cable
- 77047 — The part 77047 is an ECOCABLE featuring 2 conductors of 26 AWG tinned copper wit...
- 29521 — Belden 29521 is a Premium VFD power cable with three 14 AWG (41 x 30) tinned cop...
- 2467C — The Belden 2467C is a communication and control cable featuring four 20 AWG tinn...
- 24516D — Belden 24516D is a Canadian Instrumentation Cable (TC-ACIC) rated 600 V RMS, wit...
- 7202A — The Belden 7202A is a high-flex MachFlex™ multi-conductor cable featuring 3 pair...
- 83350E — The Belden 83350E is a high-temperature, 4-conductor 20 AWG silver-plated copper...
- 2128A — The Belden 2128A is a heavy-duty fieldbus cable designed for harsh environment d...
- 78444 — The part 78444 is an ECOCABLE featuring 25 conductors of 22 AWG stranded tinned...
1061A FAQ
What is 1061A?
1061A is a Bulk Wire Cable from Belden. The Belden 1061A is a 36-pair instrumentation and control cable featuring 20 AWG and 22 AWG bare copper conductors with PVC insulation, an overall Beld foil shield, and a black PVC outer jacket. It is rated for 300V PLTC and ITC applications with an operating temperature range of -30°C to +105°C. This cable is designed for use in industrial control systems, raceways, cable trays, DCS, PLCs, and connecting instruments, encoders, solenoids, valves, and actuators.
Who manufactures 1061A?
1061A is manufactured by Belden.
Where can I download the 1061A datasheet PDF?
The 1061A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 1061A specifications
Click to ask a quick question:
Parameters
| Conductor Configuration | 36 Pair(s) 20 AWG 7x28 BC, 1 Comm Wire(s) 22 AWG 7x30 BC |
| Max Current | 3 Amps per conductor @ 25°C |
| Nom. Capacitance Cond-to-Cond | 30 pF/ft (98 pF/m) |
| Nom. Capacitance Cond-to-Shield | 55 pF/ft (180 pF/m) |
| Nominal Outer Diameter | 0.980 in (24.9 mm) |
| Nom. Inductance | 0.19 µH/ft (0.62 µH/m) |
| Operating Temperature | -30°C to +105°C |
| Outer Shield | Bi-Laminate (Alum+Poly) Tape 100% Coverage, 20 AWG (7x28) TC Drainwire |
| UL Temperature | 105°C |
| Voltage Rating | 300 V (CMG, PLTC, UL AWM 2464), 150 V (ITC) |