1042A Datasheet
The Belden 1042A is a UL-listed instrumentation and control cable featuring 12 pairs of 16 AWG stranded bare copper conductors with PVC-nylon insulation, individual and overall Beldfoil shields, and a black PVC outer jacket. It is rated for 600V TC-ER and 150V NPLF, with a temperature range of -30°C to 90°C dry and 90°C wet. This cable is designed for use in industrial control systems, DCS, PLCs, solenoids, valves, and actuators in both dry, wet, and sunlight-resistant environments.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
1042A Key Specifications
- Max. Current
- 8 Amps per conductor @ 30°C
- Voltage Rating
- 600 V (TC-ER), 150 V (NPLF)
- Operating Temperature
- -30°C to 90°C Dry, 90°C Wet
- Bend Radius (Min. Stationary/Installation)
- 10.9 in (277 mm)
- Bulk Cable Weight
- 491 lbs/1000ft
- Conductor
- 12 pairs, 16 AWG 7x24 Bare Copper
- Max. Pull Tension
- 915 lbs (415 kg)
- Nom. Conductor DCR
- 4.2 Ohm/1000ft
Characteristics (datasheet)
- Voltage Rating
- 600 V (TC-ER), 150 V (NPLF)
- Conductor
- 12 pairs, 16 AWG 7x24 Bare Copper
- Nom. Conductor DCR
- 4.2 Ohm/1000ft
- Nom. Inner Shield DCR
- 5.49 Ohm/1000ft (18.0 Ohm/km)
- Nom. Outer Shield DCR
- 3.14 Ohm/1000ft (10.3 Ohm/km)
- Max. Current
- 8 Amps per conductor @ 30°C
- Operating Temperature
- -30°C to 90°C Dry, 90°C Wet
- Nominal Overall Diameter
- 0.907 in (23.0 mm)
- Outer Jacket Material
- PVC - Polyvinyl Chloride, Black, 0.084 in thickness with ripcord
- Shielding
- Individual & overall Bi-Laminate (Alum+Poly) tape, 100% coverage, with drain wires (18 AWG inner, 16 AWG outer)
- Max. Pull Tension
- 915 lbs (415 kg)
- Bulk Cable Weight
- 491 lbs/1000ft
- Bend Radius (Min. Stationary/Installation)
- 10.9 in (277 mm)
1042A Applications
- Industrial control
- Raceways, cable trays and ducts
- Digital control
- Instruments (4-20mA, 0-10V)
- Low voltage digital control (24V)
- Encoders
- Control circuits
- Distributed control system (DCS)
- Programmable logic controller (PLC)
- Solenoids
- Valves
- Actuators
- Positioners
Other Belden parts
- 9920 — The Belden 9920 is a low-temperature plastic lead wire featuring a 20 AWG tinned...
- 7045 — The Belden 7045 is a single-conductor, 16 AWG tinned copper hook-up wire with cr...
- 78036 — The Belden 78036 is a 6-conductor, 22 AWG tinned copper ECOCABLE with modified p...
- 5104C — The Belden 5104C (XTRAGUARD 1) is a 4-conductor, 22 AWG shielded cable designed...
- 9274 — The Belden 9274 is a discontinued RG59 coaxial cable designed for analog video a...
- 33308 — Belden 33308 is an 8 AWG (84x27) tinned copper lead wire with silicone rubber in...
- 6305 — The Belden 6305 is a 5-conductor, 24 AWG tinned copper communication and control...
- 5216C — The Belden 5216C is an XTRAGUARD 1 multi-conductor cable featuring 37 conductors...
More Bulk Wire Cable
- 86165CY — The Belden 86165CY is an XTRAGUARD FLEX 5-conductor 16 AWG tinned copper cable w...
- 4404UE — The 4404UE is a security and commercial audio cable consisting of six 20 AWG str...
- 2104A — The Belden 2104A is a high-performance fieldbus cable consisting of 12 pairs of...
- 79049 — The Belden 79049 is a multi-conductor ECOFLEX cable with 10 conductors of 22 AWG...
- 6075 — The Belden 6075 is a Teck90 600V cable designed for CEC power and control applic...
- 8846MN — The Belden 8846MN is a SpaceMaker™ 7-conductor 16AWG tinned copper cable with po...
- 76501TS — The 76501TS is a MachFlex™ high-flexibility cable featuring two 26 AWG tinned co...
- 85604 — The part 85604 is an XTRAGUARD FLEX 4-conductor, 16 AWG bare copper control cabl...
1042A FAQ
What is 1042A?
1042A is a Bulk Wire Cable from Belden. The Belden 1042A is a UL-listed instrumentation and control cable featuring 12 pairs of 16 AWG stranded bare copper conductors with PVC-nylon insulation, individual and overall Beldfoil shields, and a black PVC outer jacket. It is rated for 600V TC-ER and 150V NPLF, with a temperature range of -30°C to 90°C dry and 90°C wet. This cable is designed for use in industrial control systems, DCS, PLCs, solenoids, valves, and actuators in both dry, wet, and sunlight-resistant environments.
Who manufactures 1042A?
1042A is manufactured by Belden.
Where can I download the 1042A datasheet PDF?
The 1042A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 1042A specifications
Click to ask a quick question:
Parameters
| Bend Radius (Min. Stationary/Installation) | 10.9 in (277 mm) |
| Bulk Cable Weight | 491 lbs/1000ft |
| Conductor | 12 pairs, 16 AWG 7x24 Bare Copper |
| Max. Current | 8 Amps per conductor @ 30°C |
| Max. Pull Tension | 915 lbs (415 kg) |
| Nom. Conductor DCR | 4.2 Ohm/1000ft |
| Nominal Overall Diameter | 0.907 in (23.0 mm) |
| Nom. Inner Shield DCR | 5.49 Ohm/1000ft (18.0 Ohm/km) |
| Nom. Outer Shield DCR | 3.14 Ohm/1000ft (10.3 Ohm/km) |
| Operating Temperature | -30°C to 90°C Dry, 90°C Wet |
| Outer Jacket Material | PVC - Polyvinyl Chloride, Black, 0.084 in thickness with ripcord |
| Shielding | Individual & overall Bi-Laminate (Alum+Poly) tape, 100% coverage, with drain wires (18 AWG inner, 16 AWG outer) |
| Voltage Rating | 600 V (TC-ER), 150 V (NPLF) |